Item shown may not be actual product.
Product and price information are subject to change without notice.
Discontinued
Superseded to FLU1587FC
Product and price information are subject to change without notice.
Discontinued
Superseded to FLU1587FC
Insulation Resistance Tester
Item Number: FLU1587 - Supplier: FLUKE ELECTRONICS CORPORATION
Description
The Fluke 1587 Insulation Multimeter combines a digital insulation tester with a full-featured, true RMS digital multimeter in a single, compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.
Whether you work on motors, generators, cables, or switch gear, the Fluke 1587 Insulation Multimeter is ideally suited to help you with your tasks and at a cost that is far less than buying the two products.
Features
- Auto discharge of capacitive voltage
- Insulation test smoothing reading
- Low pass filter (for work on VSD's)
- Auto Power Off to save battery power
- True-rms
- Large display with backlight
- Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
- Accepts optional Fluke TPAKTM magnetic hanging system to free your hands for other work
Includes:
- Remote Probe
- Test Leads
- Alligator Clips
- K-Type Thermocouple
- Rigged Utility Hard Case
- Four AA Alkaline Batteries
- Quick Reference Guide
- CD Rom with Manual
Warranty
Three (3) years
Product Specifications | ||
|
Maximum Voltage: | 1000 V |
Accuracy: | ±(0.09%+2) | |
Maximum Resolution: | 0.001V | |
Voltage AC | Maximum Voltage: | 1000 V |
Acurracy: | ±(2%+3) | |
AC Bandwidth: | 5kHz (with low pass filter; 3db @ 800 Hz) | |
Maximum Resolution: | 0.1 mV | |
Current DC | Maximum Amps: | 400mA |
Amps Accuracy: | 1587: ±(0.2%+2) | |
Maximum Resolution: | 0.01 mA | |
Current AC | Maximum Amps: | 400mA |
Amps Accuracy: | ±(1.5%+2) (1kHz bandwidth) | |
Maximum Resolution: | 0.01 mA | |
Resistance | Maximum Resistance: | 50 MΩ |
Acurracy: | ±(0.9%+2) | |
Maximum Resolution: | 0.1Ω | |
Capacitance | Maximum Capacitance: | 9,999 µF |
Accuracy: | ±(1.2%+2) | |
Maximum Resolution: | 1 nF | |
Frequency | Maximum Frequency: | 100 kHz |
Accuracy: | ±(0.1%+1) | |
Maximum Resolution: | 0.01 Hz | |
Temperature Measurement | -40.0 °C to 537 °C | |
-40.0 °F to 998 °F | ||
excluding probe | ||
Diode Test | Range: | 6 V |
Resolution: | 1 mV | |
Accuracy: | ±(2 % + 1) | |
Insulation Test | ||
Minimum Test Current @ 1kΩ/V | 1mA | |
Test Voltages | 50, 100, 250, 500, 1000 V | |
Maximum Resistance per Test | 50V: | |
Voltage | 100V: | |
250V: | ||
500V: | ||
1000V: | 1587: 2 GΩ | |
Maximum Resolution per Test | 50V: | 0.01 MΩ |
Voltage | 100V: | 0.01 MΩ |
250V: | 0.1 MΩ | |
500V: | 0.1 MΩ | |
1000V: | 0.1 MΩ | |
Accuracy per Test Voltage | 50V: | ±(3 % + 5) |
100V: | ±(3 % + 5) | |
250V: | ±(1.5 % + 5) | |
500V: | 1587: ±(1.5 % + 5) | |
1000V: | 1587: ±(1.5 % + 5) to 600 MΩ, ±(10 % + 3) above 600 MΩ | |
Environmental Specifications | ||
Operating temperature | –20 °C to +55 °C | |
Storage temperature | -40°C to +60°C | |
Humidity (Without | 0% - 95% (10 °C – 30 °C) | |
Condensation) | 0% - 75% (30 °C – 40 °C) | |
0% - 40% (40 °C – 55 °C) | ||
Operating Altitude | 2000 m | |
Safety Specifications | ||
Overvoltage category | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V | |
Agency Approvals | 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V | |
Mechanical & General Specifications | ||
Size | 203 x 100 x 50 mm (with holster) | |
Weight | 624 g | |
Battery life Alkaline | Meter use: | 1000 hours |
Insulation test use: | Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. | |
IP Rating | IP40 |